The impact of location and type on the performance of Low-Voltage network connected Battery Energy Storage Systems

Yunusov, T. ORCID: https://orcid.org/0000-0003-2318-3009, Frame, D., Holderbaum, W. ORCID: https://orcid.org/0000-0002-1677-9624 and Potter, B. (2016) The impact of location and type on the performance of Low-Voltage network connected Battery Energy Storage Systems. Applied Energy, 165. pp. 202-213. ISSN 03062619

[img]
Preview
Text - Accepted Version
· Please see our End User Agreement before downloading.

1MB

It is advisable to refer to the publisher's version if you intend to cite from this work. See Guidance on citing.

To link to this item DOI: 10.1016/j.apenergy.2015.12.045

Abstract/Summary

This paper assesses the impact of the location and configuration of Battery Energy Storage Systems (BESS) on Low-Voltage (LV) feeders. BESS are now being deployed on LV networks by Distribution Network Operators (DNOs) as an alternative to conventional reinforcement (e.g. upgrading cables and transformers) in response to increased electricity demand from new technologies such as electric vehicles. By storing energy during periods of low demand and then releasing that energy at times of high demand, the peak demand of a given LV substation on the grid can be reduced therefore mitigating or at least delaying the need for replacement and upgrade. However, existing research into this application of BESS tends to evaluate the aggregated impact of such systems at the substation level and does not systematically consider the impact of the location and configuration of BESS on the voltage profiles, losses and utilisation within a given feeder. In this paper, four configurations of BESS are considered: single-phase, unlinked three-phase, linked three-phase without storage for phase-balancing only, and linked three-phase with storage. These four configurations are then assessed based on models of two real LV networks. In each case, the impact of the BESS is systematically evaluated at every node in the LV network using Matlab linked with OpenDSS. The location and configuration of a BESS is shown to be critical when seeking the best overall network impact or when considering specific impacts on voltage, losses, or utilisation separately. Furthermore, the paper also demonstrates that phase-balancing without energy storage can provide much of the gains on unbalanced networks compared to systems with energy storage.

Item Type:Article
Refereed:Yes
Divisions:Science > School of the Built Environment > Construction Management and Engineering
Life Sciences > School of Biological Sciences > Department of Bio-Engineering
Interdisciplinary centres and themes > Energy Research
Science > School of the Built Environment > Energy and Environmental Engineering group
ID Code:57178
Publisher:Elsevier

Downloads

Downloads per month over past year

University Staff: Request a correction | Centaur Editors: Update this record

Page navigation